Inductive sensor NCB5-18GM40-N0-10M

  • Comfort series
  • Usable up to SIL 2 acc. to IEC 61508
  • NAMUR sensors must be operated with approved switch amplifiers.

Specifications:

Switching function Normally closed (NC)
Output type NAMUR
Rated operating distance 5 mm
Installation flush
Assured operating distance 0 … 4.05 mm
Actual operating distance 4.5 … 5.5 mm typ. 5 mm
Reduction factor rAl 0.35
Reduction factor rCu 0.3
Reduction factor r304 0.74
Output type 2-wire
Nominal ratings
Nominal voltage 8.2 V (Ri approx. 1 kΩ)
Switching frequency 0 … 400 Hz
Hysteresis 1 … 15 typ. 5 %
Reverse polarity protection reverse polarity protected
Short-circuit protection yes
Current consumption
Measuring plate not detected min. 3 mA
Measuring plate detected ≤ 1 mA
Switching state indicator all direction LED, yellow
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
MTTFd 2040 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Compliance with standards and directives
Standard conformity
NAMUR EN 60947-5-6:2000
IEC 60947-5-6:1999
Standards EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
IECEx approval yes
Equipment protection level Ga IECEx PTB 11.0037X
Equipment protection level Gb IECEx PTB 11.0037X
Equipment protection level Da IECEx PTB 11.0037X
Equipment protection level Dc (tc) IECEx TUR 21.0018X
Equipment protection level Mb IECEx PTB 11.0037X
ATEX approval yes
Equipment protection level Ga PTB 00 ATEX 2048 X
Equipment protection level Gb PTB 00 ATEX 2048 X
Equipment protection level Da PTB 00 ATEX 2048 X
Equipment protection level Dc (tc) TÜV 20 ATEX 8524 X
EAC conformity TR CU 012/2011
UL approval yes
Ordinary Location E87056
Hazardous Location E501628
Control drawing 116-0452
CCC approval
NEPSI approval yes
NEPSI certificate GYJ16.1393X
ANZEx 18.3018X
KCC approval yes
Hazardous Location 09-AV4BO-0226

Description

  • 22 mm quasi flush
  • Increased operating distance