TURCK IM1-22EX-R/24VDC Amplifier Isolating Switching 2 Channel 24VDC M7541210

Specifications:

Type designation:  IM1-22EX-R
Ident no. : 7541231
Nominal voltage:  Universal voltage supply unit
Operating voltage:  20…250 VAC
Frequency:  40…70 Hz
Operating voltage range:  20…125 VDC
Power consumption:  ð 3 W
Power dissipation, typ.:  ð 0.98 W
NAMUR input
NAMUR EN : 60947-5-6
Input circuit monitoring : on/off switchable
No-load voltage:  8.2 VDC
Short-circuit current:  8.2 mA
Input resistance:  1 kò
Cable resistance: ð 50 ò
Switch-on threshold: 1.75 mA
Switch-off threshold: 1.55 mA
Wire breakage threshold: ð 0.06 mA
Short-circuit threshold: ï 6.4 mA
Output circuits (digital) : 2 x relays (NO)
Output switching voltage relay : ð 30 VDC / ð 250 VAC
Switching current per output: ð 2 A
Switching capacity per output: ð 500 VA/60 W
Switching frequency : ð 10 Hz
Contact quality: AgNi, 3µ Au
Galvanic isolation
Test voltage : 2.5 kV

Indication
Operational: readiness green
Switching state: Yellow
State/ Fault: 2 × yellow/red
Error indication: red

Description

The 2-channel IM1-22EX-R isolating switching amplifier is equipped with intrinsically safe input circuits.Sensors according to EN 60947-5-6 (NAMUR)or potential-free contact transmitters can be connected to the device.The output circuits feature 2 relays, each with 1 NO contact.
Via six switches on the front, you can set the operating behaviour for each channel separately and short-circuit monitoring (SC) on and off.
When using mechanical contacts, wire-break and short-circuit monitoring must be switchedoff or the contacts must be wired to resistors(II) (see circuit diagram).The Pwr LED lights green to indicate operational readiness. The 2-color LEDs 1 and 2 light yellow to indicate the switching status of the associated output. In the event of an input circuit error, the 2-color LED of the assigned faulty input turns red, with the input circuit monitoring switched on. Thereupon the output relay drops out.