VBC6-30-10 GJL1213901R0107 ABB VBC6-30-10-07 Mini Reversing Contactor

Specifications:

Dimensions

  • Product Net Width: 96.5mm
  • Product Net Height: 57.5mm
  • Product Net Depth: 46.5mm
  • Product Net Weight: 0.355kg

Container Information

  • Package Level 1 Units: 5 piece
  • Package Level 1 Width: 115 mm
  • Package Level 1 Height: 54 mm
  • Package Level 1 Length: 280 mm
  • Package Level 1 Gross Weight: 1.845 kg
  • Package Level 1 EAN: 4013614415852

Environmental

  • Ambient Air Temperature:
    Operation -20 … +55 °C
    Storage -40 … +80 °C
  • Maximum Operating Altitude Permissible: 2000 m
  • Resistance to Shock acc. to IEC 60068-2-27: 11 ms Pulse 15g
  • Resistance to Vibrations acc. to IEC 60068-2-6: 5g / 5 … 150 Hz
  • RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment

Technical

  • Contactor Starter Type: Compact Reversing Contactor with Normal Interlock
  • Number of Auxiliary Contacts NC: 0
  • Number of Auxiliary Contacts NO: 1
  • Number of Main Contacts NC: 0
  • Number of Main Contacts NO: 3
  • Number of Poles: 4
  • Pollution Degree: 3
  • Rated Frequency (f):
    Control Circuit DC
    Main Circuit 60 Hz
    Main Circuit 50 Hz
    Main Circuit DC
  • Rated Impulse Withstand Voltage (Uimp): Main Circuit 6 kV
  • Rated Insulation Voltage (Ui):
    690 V
    acc. to UL/CSA 600 V
  • Rated Operational Current AC-1 (Ie):
    (220 / 240 V) 40 °C 20 A
    (220 / 240 V) 55 °C 16 A
    (380 / 440 V) 40 °C 20 A
    (380 / 440 V) 55 °C 16 A
    (690 V) 40 °C 6 A
    (690 V) 55 °C 6 A
  • Rated Operational Current AC-3 (Ie):
    (220 / 230 / 240 V) 55 °C 9 A
    (380 / 400 V) 55 °C 8.5 A
    (440 V) 55 °C 8 A
    (500 V) 55 °C 5.5 A
    (690 V) 55 °C 3.5 A
  • Rated Operational Voltage: Main Circuit 690 V AC
  • Conventional Free-air Thermal Current (Ith): Main Circuit 20 A
  • Rated Control Circuit Voltage (Uc): 12 V DC
  • Coil Operating Limits: (acc. to IEC 60947-4-1) for DC supply 0.85 … 1.1 x Uc (at θ ≤ 55 °C)
  • Degree of Protection:
    Auxiliary Circuit Terminals IP20
    Control Circuit Terminals IP20
    Main Circuit Terminals IP20
  • Mechanical Durability: 10000000 cycle
  • Connecting Capacity-Main Circuit:
    Flexible with Ferrule 1/2x 1 … 2.5 mm²
    Flexible with Insulated Ferrule 1/2x 1 … 2.5 mm²
    Flexible 1/2x 1 … 2.5 mm²
    Rigid 1/2x 1 … 4 mm²
  • Connecting Capacity-Auxiliary Circuit:
    Flexible with Ferrule 1/2x 1 … 2.5 mm²
    Flexible with Insulated Ferrule 1/2x 1 … 2.5 mm²
    Flexible 1/2x 1 … 2.5 mm²
    Rigid 1/2x 1 … 4 mm²
  • Connecting Capacity-Control Circuit:
    Flexible with Ferrule 1/2x 1 … 2.5 mm²
    Flexible with Insulated Ferrule 1/2x 1 … 2.5 mm²
    Flexible 1/2x 1 … 2.5 mm²
    Rigid 1/2x 1 … 4 mm²
  • Tightening Torque:
    Control Circuit 0.8 … 1.1 N·m
    Main Circuit 0.8 … 1.1 N·m
  • Wire Stripping Length:
    Auxiliary Circuit 9 mm
    Main Circuit 9 mm
  • Mounting on DIN Rail:
    TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
    TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
  • Power Loss:
    at Rated Operating Conditions per Pole 2 W
  • Standards:
    IEC/EN 60947-1
    IEC/EN 60947-4-1
    IEC/EN 60947-5-1
    UL 60947-1
    UL 60947-4-1

Technical UL/CSA

  • Maximum Operating Voltage UL/CSA:
    Main Circuit 600 V AC
  • Horsepower Rating UL/CSA:
    (208 V AC) Three Phase 1 Hp
    (220 … 240 V AC) Single Phase 0.5 Hp
    (220 … 240 V AC) Three Phase 2 Hp
    (440 … 480 V AC) Three Phase 3 Hp
    (550 … 600 V AC) Three Phase 1 Hp
  • General Use Rating UL/CSA:
    (300 V AC) 12 A
  • Connecting Capacity Main Circuit UL/CSA:
    Stranded 1/2x 22 … 10 AWG
  • Connecting Capacity Auxiliary Circuit UL/CSA:
    Stranded 1/2x 22 … 10 AWG
  • Tightening Torque UL/CSA:
    Auxiliary Circuit 7 in·lb
    Control Circuit 7 in·lb
    Main Circuit 7 in·lb

Certificates and Declarations (Document Number)

Classifications

  • Object Classification Code: Q
  • eClass: 7.0 27371009
  • ETIM 4: EC000066 – Magnet contactor, AC-switching
  • ETIM 5: EC000010 – Starter combination
  • UNSPSC: 39121529

Description

The VBC6-30-10 mini reversing contactor is a compact 3 pole contactor with 1 auxiliary contact, screw terminals and normal mechanical interlock. They are ideally suited for applications where reliability is a must and space is at a premium. Mini reversing contactors are used in residential buldings, commercial buildings and industrial applications for the control of three-phase motor loads up to 4 kW (AC-3). Further features are the noiseless and hum-free coil, a a switch position indication and the integrated possibility for rail or wall mounting.